ioLogik 4000 Series

Introduction
The ioLogik 4000 Series is suitable for remote monitoring and alarm systems, such as those used for water treatment systems, water supply systems, wastewater treatment systems, and power monitoring systems. These kinds of applications need more I/O points and a variety of I/O types, including temperature sensors, gas detectors, and water quality detectors, all of which can benefit from the versatile mixture of I/O features supported by the ioLogik 4000 Series.

Slice Form Factor and Flexible I/O Variety
The unique modular construction of the ioLogik 4000 Series allows for mixing and matching of modules to achieve the best combination of I/O modules to meet the needs of a wide range of remote automation applications. An industrial modular housing enables I/O modules to be added to the base unit without a backplane. The ioLogik 4000 Series is perfect for space-limited applications, and high-density I/O points are provided for greater flexibility and expandability. Modules can connect to virtually any type of sensor, including but not limited to those for temperature, pressure, flow, voltage, current, and contact closure.

 

Easy Maintenance
The ioLogik 4000 Series comes with removable spring-type terminal blocks (RTBs) that allow you to conserve field wiring for future use.

ioLogik 4000 Series

Features and Benefits

  • I/O expansion without a backplane
  • Active communication with MX-AOPC UA Server
  • Supports SNMP v1/v2c
  • Easy configuration with Modular ioAdmin utility
  • Friendly configuration via web browser
  • Simplifies I/O management with MXIO library for Windows or Linux

Certifications

Download Datasheet

View List

Description

Introduction
The ioLogik 4000 Series is suitable for remote monitoring and alarm systems, such as those used for water treatment systems, water supply systems, wastewater treatment systems, and power monitoring systems. These kinds of applications need more I/O points and a variety of I/O types, including temperature sensors, gas detectors, and water quality detectors, all of which can benefit from the versatile mixture of I/O features supported by the ioLogik 4000 Series.

Slice Form Factor and Flexible I/O Variety
The unique modular construction of the ioLogik 4000 Series allows for mixing and matching of modules to achieve the best combination of I/O modules to meet the needs of a wide range of remote automation applications. An industrial modular housing enables I/O modules to be added to the base unit without a backplane. The ioLogik 4000 Series is perfect for space-limited applications, and high-density I/O points are provided for greater flexibility and expandability. Modules can connect to virtually any type of sensor, including but not limited to those for temperature, pressure, flow, voltage, current, and contact closure.

 

Easy Maintenance
The ioLogik 4000 Series comes with removable spring-type terminal blocks (RTBs) that allow you to conserve field wiring for future use.

Specification

LanguageioLogik E4200: Click&Go, NA-4010/4020/4021: None

10/100BaseT(X) Ports (RJ45 connector)NA-4010: 1
ioLogik E4200: 2, 2 MAC addresses

Configuration OptionsNA-4010/ioLogik E4200: Web Console (HTTP)
NA-4010/4020/4021: Windows Utility (ioAdmin)
ioLogik E4200: Windows Utility (Modular-ioAdmin)
Industrial ProtocolsNA-4010: Modbus TCP Server (Slave), MXIO Library
NA-4020/4021: MXIO Library
ioLogik E4200: Modbus TCP Server (Slave), Moxa AOPC (Active Tag), MXIO Library, SNMPv1/v2c, SNMPv1 Trap
ManagementNA-4010/ioLogik E4200: DHCP Client, HTTP, IPv4, TCP/IP, UDP
NA-4010/4020/4021: ioAdmin
ioLogik E4200: Modular-ioAdmin

BaudrateNA-4020/4021: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
ConnectorNA-4021: DB9 female
NA-4020: Terminal block
No. of Ports1
ParityNone, Even, Odd
Serial StandardsNA-4021: RS-232
NA-4020: RS-485
Data Bits7, 8
Stop Bits1, 2

Industrial ProtocolsNA-4020/4021: Modbus RTU/ASCII Slave

RS-232NA-4021: TxD, RxD, GND
RS-485-2wNA-4020: Data+, Data-, GND

Serial InterfaceFixed baudrate

Max. No. of Client Connections8
ModeClient (Master)

No. of Power Inputs1

Power ConnectorSpring-type Euroblock terminal
No. of Power Inputs1
Input Voltage11 to 28.8 VDC
Power ConsumptionNA-4010: 60 mA @ 24 VDC
NA-4020/4021: 70 mA @ 24 VDC
ioLogik E4200: 175 mA @ 24 VDC

Power ConnectorSpring-type Euroblock terminal
No. of Power Inputs1
Input Voltage11 to 28.8 VDC
Current in Field Power Contact10 A (max.)

HousingPlastic
IP RatingIP30
Dimensions45 x 99 x 70 mm (1.77 x 3.90 x 2.76 in)
WeightNA-4010/4020/4021: 150 g (0.33 lb)
ioLogik E4200: 180 g (0.396 lb)
InstallationDIN-rail mounting

Operating Temperature-10 to 60°C (14 to 140°F)
Storage Temperature (package included)-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity5 to 95% (non-condensing)
Altitude2000 m

SafetyUL 508
EMCEN 61000-6-2/-6-4
EMICISPR 32, FCC Part 15B Class A
EMSIEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
ShockIEC 60068-2-27
VibrationIEC 60068-2-6

Green ProductRoHS, CRoHS, WEEE

TimeNA-4010: 4,739,300 hrs
NA-4020: 4,721,640 hrs
NA-4021: 4,695,360 hrs
ioLogik E4200: 357,000 hrs
StandardsTelcordia SR332

Warranty Period2 years
DetailsSee www.moxa.com/warranty