TCC-100/100I Series

Introduction
The TCC-100/100I Series of RS-232 to RS-422/485 converters increases networking capability by extending the RS-232 transmission distance. Both converters have a superior industrial-grade design that includes DIN-rail mounting, terminal block wiring, an external terminal block for power, and optical isolation (TCC-100I and TCC-100I-T only). The TCC-100/100I Series converters are ideal solutions for converting RS-232 signals to RS-422/485 in critical industrial environments.

TCC-100/100I Series

Features and Benefits

  • RS-232 to RS-422 conversion with RTS/CTS support
  • RS-232 to 2-wire or 4-wire RS-485 conversion
  • 2 kV isolation protection (TCC-100I)
  • Wall mounting and DIN-rail mounting
  • Plug-in terminal block for easy RS-422/485 wiring
  • LED indicators for power, Tx, Rx
  • Wide-temperature model available for -40 to 85°C environments

Certifications

Download Datasheet

Description

Introduction
The TCC-100/100I Series of RS-232 to RS-422/485 converters increases networking capability by extending the RS-232 transmission distance. Both converters have a superior industrial-grade design that includes DIN-rail mounting, terminal block wiring, an external terminal block for power, and optical isolation (TCC-100I and TCC-100I-T only). The TCC-100/100I Series converters are ideal solutions for converting RS-232 signals to RS-422/485 in critical industrial environments.

Specification

RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND

Input Current TCC-100/100-T: 50 to 85 mA @ 12 to 48 VDC
TCC-100I/100I-T: 150 mA @ 12 to 48 VDC
Input Voltage 12 to 48 VDC
No. of Power Inputs 1
Overload Current Protection Supported
Power Connector Terminal block (for DC models)
Power Consumption TCC-100/100-T: 50 to 85 mA @ 12 to 48 VDC
TCC-100I/100I-T: 150 mA @ 12 to 48 VDC

Housing Metal
IP Rating IP30
Dimensions 67 x 100.4 x 22 mm (2.64 x 3.93 x 0.87 in)
Weight 148 g (0.33 lb)
Installation DIN-rail mounting (with optional kit), Wall mounting

Operating Temperature Standard Models: -20 to 60°C (-4 to 140°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Storage Temperature (package included) -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)

EMC EN 55032/24
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 1 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 3 V/m; Signal: 3 V/m
IEC 61000-4-8 PFMF
Environmental Testing IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-3
Safety EN 60950-1, IEC 60950-1
Vibration IEC 60068-2-6

Time 3,017,857 hrs
Standards Telcordia (Bellcore), GB

Warranty Period 5 years
Details See www.moxa.com/warranty

Models