ioLogik R1200 Series

Introduction
The ioLogik R1200 Series RS-485 serial remote I/O devices are perfect for establishing a cost-effective, dependable, and easy-to-maintain remote process control I/O system. Remote serial I/O products offer process engineers the benefit of simple wiring, as they only require two wires to communicate with the controller and other RS-485 devices while adopting the EIA/TIA RS-485 communication protocol to transmit and receive data at high speed over long distances. In addition to communication configuration by software or USB and dual RS-485 port design, Moxa’s remote I/O devices eliminate the nightmare of extensive labor associated with the setup and maintenance of data acquisition and automation systems. Moxa also offers different I/O combinations, which provide greater flexibility and are compatible with many different applications.

Easy-to-Use Software Interface for Easy Maintenance
With Moxa’s easy-to-use ioSearch software, you can quickly access all of an ioLogik R1200 device’s status information and settings with a user-friendly graphical user interface. Furthermore, ioSearch also provides an easy method for updating firmware for all ioLogik R1200 devices over an RS-485 network, so you can even update your firmware remotely. The free and easy-to-use ioSearch software reduces the maintenance time and labor required to set up your communication interface. When more than one ioLogik R1200 are on the same RS-485 network, you no longer need to turn hundreds of dials during setup. Instead, simply configure and duplicate each ioLogik R1200’s baudrate and mode through the graphical user interface. This convenient software feature reduces maintenance engineers’ effort, and greatly simplifies upgrading your device’s configuration compared with more traditional methods.

 

Innovative Hardware Design Reduces Deployment Effort and Enhances Maintenance Efficiency
With the industry’s first RS-485 serial remote I/O with USB design, Moxa provides an innovative solution for upgrading and configuring RS-485 remote I/O communication devices and firmware. All you need to do is upload the configurations to a USB drive, plug it into the field device, and all the configurations and firmware updates will upload to the field device automatically.

 

Cost-Saving Hardware Design for Backup and Redundancy
Moxa’s ioLogik R1200 Series provides dual RS-485 ports so that when one of your RS-485 ports is damaged, you can quickly switch to the other RS-485 port for quick testing or repair. RS-485 remote I/O devices are already considered a low-cost technology, but with dual RS-485 ports, Moxa helps you save a little bit more. With the ioLogik R1200, you can take advantage of our dual RS-485 ports to set up wiring, provide computer redundancy, or back up your network using two computer topologies. For wiring redundancy, when your computer detects that one of the RS-485 connections is not responding, it can quickly switch over to the other RS-485 line to guarantee continuous communication between field sensors and the central computer. Furthermore, users have the freedom to define the settings. For computer redundancy, the ioLogik R1200 provides system operators with a secure backup when one system goes down.

ioLogik R1200 Series

Features and Benefits

  • Dual RS-485 remote I/O with built-in repeater
  • Supports the installation of multidrop communications parameters
  • Install communications parameters and upgrade firmware via USB
  • Upgrade firmware through an RS-485 connection
  • Wide operating temperature models available for -40 to 85°C (-40 to 185°F) environments

Certifications

Download Datasheet

View List

Description

Introduction
The ioLogik R1200 Series RS-485 serial remote I/O devices are perfect for establishing a cost-effective, dependable, and easy-to-maintain remote process control I/O system. Remote serial I/O products offer process engineers the benefit of simple wiring, as they only require two wires to communicate with the controller and other RS-485 devices while adopting the EIA/TIA RS-485 communication protocol to transmit and receive data at high speed over long distances. In addition to communication configuration by software or USB and dual RS-485 port design, Moxa’s remote I/O devices eliminate the nightmare of extensive labor associated with the setup and maintenance of data acquisition and automation systems. Moxa also offers different I/O combinations, which provide greater flexibility and are compatible with many different applications.

Easy-to-Use Software Interface for Easy Maintenance
With Moxa’s easy-to-use ioSearch software, you can quickly access all of an ioLogik R1200 device’s status information and settings with a user-friendly graphical user interface. Furthermore, ioSearch also provides an easy method for updating firmware for all ioLogik R1200 devices over an RS-485 network, so you can even update your firmware remotely. The free and easy-to-use ioSearch software reduces the maintenance time and labor required to set up your communication interface. When more than one ioLogik R1200 are on the same RS-485 network, you no longer need to turn hundreds of dials during setup. Instead, simply configure and duplicate each ioLogik R1200’s baudrate and mode through the graphical user interface. This convenient software feature reduces maintenance engineers’ effort, and greatly simplifies upgrading your device’s configuration compared with more traditional methods.

 

Innovative Hardware Design Reduces Deployment Effort and Enhances Maintenance Efficiency
With the industry’s first RS-485 serial remote I/O with USB design, Moxa provides an innovative solution for upgrading and configuring RS-485 remote I/O communication devices and firmware. All you need to do is upload the configurations to a USB drive, plug it into the field device, and all the configurations and firmware updates will upload to the field device automatically.

 

Cost-Saving Hardware Design for Backup and Redundancy
Moxa’s ioLogik R1200 Series provides dual RS-485 ports so that when one of your RS-485 ports is damaged, you can quickly switch to the other RS-485 port for quick testing or repair. RS-485 remote I/O devices are already considered a low-cost technology, but with dual RS-485 ports, Moxa helps you save a little bit more. With the ioLogik R1200, you can take advantage of our dual RS-485 ports to set up wiring, provide computer redundancy, or back up your network using two computer topologies. For wiring redundancy, when your computer detects that one of the RS-485 connections is not responding, it can quickly switch over to the other RS-485 line to guarantee continuous communication between field sensors and the central computer. Furthermore, users have the freedom to define the settings. For computer redundancy, the ioLogik R1200 provides system operators with a secure backup when one system goes down.

Specification

ConnectorScrew-fastened Euroblock terminal
Counter Frequency2.5 kHz
Digital Filtering Time IntervalSoftware configurable
Dry ContactOn: short to GND
Off: open
I/O ModeDI or event counter
Points per COMioLogik R1210/R1212 Series: 8 channels
ioLogik R1214 Series: 6 channels
Sensor TypeDry contact
Wet Contact (NPN or PNP)
Wet Contact (DI to COM)On: 10 to 30 VDC
Off: 0 to 3 VDC

ConnectorScrew-fastened Euroblock terminal
I/O TypeSink
I/O ModeDO or pulse output
Current Rating200 mA per channel
Pulse Output Frequency5 kHz
DIO Output Leakage Current4.0 mA @ 24 VDC
Over-Current Protection0.65 A per channel @ 25°C
Over-Temperature Shutdown175°C (typical), 150°C (min.)
Over-Voltage Protection45 VDC (typical)

Breakdown Voltage500 VAC
ConnectorScrew-fastened Euroblock terminal
Contact Current RatingResistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Contact Resistance100 milli-ohms (max.)
Electrical Endurance100,000 operations @ 5 A resistive load
Initial Insulation Resistance1,000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance5,000,000 operations
Pulse Output Frequency0.3 Hz at rated load
TypeForm A (N.O.) power relay
NoteAmbient humidity must be non-condensing and remain between 5 and 95%. The relays may malfunction when operating in high condensation environments below 0°C.

ConnectorScrew-fastened Euroblock terminal
I/O ModeVoltage/Current
I/O TypeDifferential
Resolution16 bits
Input Range0 to 10 VDC
0 to 20 mA
4 to 20 mA
4 to 20 mA (with burn-out detection)
AccuracyioLogik R1240:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°CioLogik R1240-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
±0.5% FSR @ -40 to 75°C
Sampling RateAll channels: 12 samples/sec
Per channel: 1.5 samples/sec
Only one channel enabled: 12 samples/sec
Built-in Resistor for Current Input120 ohms
Input Impedance10 mega-ohms (min.)

ConnectorScrew-fastened Euroblock terminal
Output Range0 to 10 VDC
0 to 20 mA
4 to 20 mA
Resolution12-bit
AccuracyioLogik R1241:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°CioLogik R1241-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Voltage Output10 mA (max.)
Load (Current Mode)Internal power: 400 ohms (max.)
24 V external power: 1000 ohms (max.)

LED IndicatorsPWR, RDY, P1, P2

Baudrate1200 bps to 921.6 kbps
ConnectorTerminal block
No. of Ports2
ParityNone
Even
Odd
Pull High/Low Resistor for RS-4851 kilo-ohm, 150 kilo-ohms
Serial StandardsRS-485
Stop Bits1, 2
Surge1 kVESD15 kVData Bits8Flow ControlNoneXON/XOFF

RS-485-2wData+, Data-, GND

Industrial ProtocolsModbus RTU Master

Power ConnectorScrew-fastened Euroblock terminal
No. of Power Inputs1
Input Voltage12 to 48 VDC
Power ConsumptionioLogik R1210 Series: 154 mA @ 24 VDC
ioLogik R1212 Series: 187 mA @ 24 VDC
ioLogik R1214 Series: 207 mA @ 24 VDC
ioLogik R1240 Series: 216 mA @ 24 VDC
ioLogik R1241 Series: 343 mA @ 24 VDC

HousingPlastic
Dimensions27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight200 g (0.44 lb)
InstallationDIN-rail mounting, Wall mounting
WiringI/O cable, 16 to 26 AWG
Power cable, 12 to 24 AWG

Operating TemperatureStandard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature (package included)-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity5 to 95% (non-condensing)
Altitude2000 m

SafetyUL 508
EMCEN 55032/24
EMICISPR 32, FCC Part 15B Class A
EMSIEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
ShockIEC 60068-2-27
VibrationIEC 60068-2-6

Green ProductRoHS, CRoHS, WEEE

Time1,239,293 hrs
StandardsTelcordia SR332

Warranty PeriodioLogik R1214: 2 years
ioLogik R1210/R1212/R1240/R1241 Series: 5 years
DetailsSee www.moxa.com/warranty