ioLogik R1200 Series

Introduction
The ioLogik R1200 Series RS-485 serial remote I/O devices are perfect for establishing a cost-effective, dependable, and easy-to-maintain remote process control I/O system. Remote serial I/O products offer process engineers the benefit of simple wiring, as they only require two wires to communicate with the controller and other RS-485 devices while adopting the EIA/TIA RS-485 communication protocol to transmit and receive data at high speed over long distances. In addition to communication configuration by software or USB and dual RS-485 port design, Moxa’s remote I/O devices eliminate the nightmare of extensive labor associated with the setup and maintenance of data acquisition and automation systems. Moxa also offers different I/O combinations, which provide greater flexibility and are compatible with many different applications.

Easy-to-Use Software Interface for Easy Maintenance
With Moxa’s easy-to-use ioSearch software, you can quickly access all of an ioLogik R1200 device’s status information and settings with a user-friendly graphical user interface. Furthermore, ioSearch also provides an easy method for updating firmware for all ioLogik R1200 devices over an RS-485 network, so you can even update your firmware remotely. The free and easy-to-use ioSearch software reduces the maintenance time and labor required to set up your communication interface. When more than one ioLogik R1200 are on the same RS-485 network, you no longer need to turn hundreds of dials during setup. Instead, simply configure and duplicate each ioLogik R1200’s baudrate and mode through the graphical user interface. This convenient software feature reduces maintenance engineers’ effort, and greatly simplifies upgrading your device’s configuration compared with more traditional methods.

 

Innovative Hardware Design Reduces Deployment Effort and Enhances Maintenance Efficiency
With the industry’s first RS-485 serial remote I/O with USB design, Moxa provides an innovative solution for upgrading and configuring RS-485 remote I/O communication devices and firmware. All you need to do is upload the configurations to a USB drive, plug it into the field device, and all the configurations and firmware updates will upload to the field device automatically.

 

Cost-Saving Hardware Design for Backup and Redundancy
Moxa’s ioLogik R1200 Series provides dual RS-485 ports so that when one of your RS-485 ports is damaged, you can quickly switch to the other RS-485 port for quick testing or repair. RS-485 remote I/O devices are already considered a low-cost technology, but with dual RS-485 ports, Moxa helps you save a little bit more. With the ioLogik R1200, you can take advantage of our dual RS-485 ports to set up wiring, provide computer redundancy, or back up your network using two computer topologies. For wiring redundancy, when your computer detects that one of the RS-485 connections is not responding, it can quickly switch over to the other RS-485 line to guarantee continuous communication between field sensors and the central computer. Furthermore, users have the freedom to define the settings. For computer redundancy, the ioLogik R1200 provides system operators with a secure backup when one system goes down.

ioLogik R1200 Series

Features and Benefits

  • Dual RS-485 remote I/O with built-in repeater
  • Supports the installation of multidrop communications parameters
  • Install communications parameters and upgrade firmware via USB
  • Upgrade firmware through an RS-485 connection
  • Wide operating temperature models available for -40 to 85°C (-40 to 185°F) environments

Certifications

Download Datasheet

Description

Introduction
The ioLogik R1200 Series RS-485 serial remote I/O devices are perfect for establishing a cost-effective, dependable, and easy-to-maintain remote process control I/O system. Remote serial I/O products offer process engineers the benefit of simple wiring, as they only require two wires to communicate with the controller and other RS-485 devices while adopting the EIA/TIA RS-485 communication protocol to transmit and receive data at high speed over long distances. In addition to communication configuration by software or USB and dual RS-485 port design, Moxa’s remote I/O devices eliminate the nightmare of extensive labor associated with the setup and maintenance of data acquisition and automation systems. Moxa also offers different I/O combinations, which provide greater flexibility and are compatible with many different applications.

Easy-to-Use Software Interface for Easy Maintenance
With Moxa’s easy-to-use ioSearch software, you can quickly access all of an ioLogik R1200 device’s status information and settings with a user-friendly graphical user interface. Furthermore, ioSearch also provides an easy method for updating firmware for all ioLogik R1200 devices over an RS-485 network, so you can even update your firmware remotely. The free and easy-to-use ioSearch software reduces the maintenance time and labor required to set up your communication interface. When more than one ioLogik R1200 are on the same RS-485 network, you no longer need to turn hundreds of dials during setup. Instead, simply configure and duplicate each ioLogik R1200’s baudrate and mode through the graphical user interface. This convenient software feature reduces maintenance engineers’ effort, and greatly simplifies upgrading your device’s configuration compared with more traditional methods.

 

Innovative Hardware Design Reduces Deployment Effort and Enhances Maintenance Efficiency
With the industry’s first RS-485 serial remote I/O with USB design, Moxa provides an innovative solution for upgrading and configuring RS-485 remote I/O communication devices and firmware. All you need to do is upload the configurations to a USB drive, plug it into the field device, and all the configurations and firmware updates will upload to the field device automatically.

 

Cost-Saving Hardware Design for Backup and Redundancy
Moxa’s ioLogik R1200 Series provides dual RS-485 ports so that when one of your RS-485 ports is damaged, you can quickly switch to the other RS-485 port for quick testing or repair. RS-485 remote I/O devices are already considered a low-cost technology, but with dual RS-485 ports, Moxa helps you save a little bit more. With the ioLogik R1200, you can take advantage of our dual RS-485 ports to set up wiring, provide computer redundancy, or back up your network using two computer topologies. For wiring redundancy, when your computer detects that one of the RS-485 connections is not responding, it can quickly switch over to the other RS-485 line to guarantee continuous communication between field sensors and the central computer. Furthermore, users have the freedom to define the settings. For computer redundancy, the ioLogik R1200 provides system operators with a secure backup when one system goes down.

Specification

Connector Screw-fastened Euroblock terminal
Counter Frequency 2.5 kHz
Digital Filtering Time Interval Software configurable
Dry Contact On: short to GND
Off: open
I/O Mode DI or event counter
Points per COM ioLogik R1210/R1212 Series: 8 channels
ioLogik R1214 Series: 6 channels
Sensor Type Dry contact
Wet Contact (NPN or PNP)
Wet Contact (DI to COM) On: 10 to 30 VDC
Off: 0 to 3 VDC

Connector Screw-fastened Euroblock terminal
I/O Type Sink
I/O Mode DO or pulse output
Current Rating 200 mA per channel
Pulse Output Frequency 5 kHz
DIO Output Leakage Current 4.0 mA @ 24 VDC
Over-Current Protection 0.65 A per channel @ 25°C
Over-Temperature Shutdown 175°C (typical), 150°C (min.)
Over-Voltage Protection 45 VDC (typical)

Breakdown Voltage 500 VAC
Connector Screw-fastened Euroblock terminal
Contact Current Rating Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Contact Resistance 100 milli-ohms (max.)
Electrical Endurance 100,000 operations @ 5 A resistive load
Initial Insulation Resistance 1,000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance 5,000,000 operations
Pulse Output Frequency 0.3 Hz at rated load
Type Form A (N.O.) power relay
Note Ambient humidity must be non-condensing and remain between 5 and 95%. The relays may malfunction when operating in high condensation environments below 0°C.

Connector Screw-fastened Euroblock terminal
I/O Mode Voltage/Current
I/O Type Differential
Resolution 16 bits
Input Range 0 to 10 VDC
0 to 20 mA
4 to 20 mA
4 to 20 mA (with burn-out detection)
Accuracy ioLogik R1240:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°CioLogik R1240-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
±0.5% FSR @ -40 to 75°C
Sampling Rate All channels: 12 samples/sec
Per channel: 1.5 samples/sec
Only one channel enabled: 12 samples/sec
Built-in Resistor for Current Input 120 ohms
Input Impedance 10 mega-ohms (min.)

Connector Screw-fastened Euroblock terminal
Output Range 0 to 10 VDC
0 to 20 mA
4 to 20 mA
Resolution 12-bit
Accuracy ioLogik R1241:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°CioLogik R1241-T:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Voltage Output 10 mA (max.)
Load (Current Mode) Internal power: 400 ohms (max.)
24 V external power: 1000 ohms (max.)

LED Indicators PWR, RDY, P1, P2

Baudrate 1200 bps to 921.6 kbps
Connector Terminal block
No. of Ports 2
Parity None
Even
Odd
Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohms
Serial Standards RS-485
Stop Bits 1, 2
Surge 1 kVESD15 kVData Bits8Flow ControlNoneXON/XOFF

RS-485-2w Data+, Data-, GND

Industrial Protocols Modbus RTU Master

Power Connector Screw-fastened Euroblock terminal
No. of Power Inputs 1
Input Voltage 12 to 48 VDC
Power Consumption ioLogik R1210 Series: 154 mA @ 24 VDC
ioLogik R1212 Series: 187 mA @ 24 VDC
ioLogik R1214 Series: 207 mA @ 24 VDC
ioLogik R1240 Series: 216 mA @ 24 VDC
ioLogik R1241 Series: 343 mA @ 24 VDC

Housing Plastic
Dimensions 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight 200 g (0.44 lb)
Installation DIN-rail mounting, Wall mounting
Wiring I/O cable, 16 to 26 AWG
Power cable, 12 to 24 AWG

Operating Temperature Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature (package included) -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude 2000 m

Safety UL 508
EMC EN 55032/24
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
Shock IEC 60068-2-27
Vibration IEC 60068-2-6

Green Product RoHS, CRoHS, WEEE

Time 1,239,293 hrs
Standards Telcordia SR332

Warranty Period ioLogik R1214: 2 years
ioLogik R1210/R1212/R1240/R1241 Series: 5 years
Details See www.moxa.com/warranty

Models