ioPAC 8500 Series (85M) Modules

Introduction
Moxa’s ioPAC 8500 Series 85M Modules can be installed in both ioPAC 8500 and ioPAC 8600 Series devices. Modules are available with DI/Os, AIs, Fast AIs, and serial interfaces, giving users a wide variety of options to choose from and allowing them to select the I/O combination that best fits their target application. All 85M modules are designed for railway industry applications, and as such, are compliant with EN 50121-3-2, EN 50121-4, and a portion of the EN 50155 specifications. In addition, these modules all support a wide operating temperature range of -40 to 75°C for reliable operation even in harsh environments.

ioPAC 8500 Series (85M) Modules

Features and Benefits

  • Compliant with EN 50121-3-2, EN 50121-4, and a portion of EN 50155 specifications
  • Rugged and compact design for harsh environments
  • Expand the I/O and communication capabilities of your ioPAC 8600 or 8500 Series device
  • Wide operating temperature range: -40 to 75°C (-40 to 167°F)
  • Millisecond timestamp granularity for digital input and analog input
  • Supports sampling rates up to 40 kHz for analog input
  • Pre-recording for analog input data logging
  • Up to 4 3-in-1 RS-232/422/485 serial ports

Certifications

Download Datasheet

Description

Introduction
Moxa’s ioPAC 8500 Series 85M Modules can be installed in both ioPAC 8500 and ioPAC 8600 Series devices. Modules are available with DI/Os, AIs, Fast AIs, and serial interfaces, giving users a wide variety of options to choose from and allowing them to select the I/O combination that best fits their target application. All 85M modules are designed for railway industry applications, and as such, are compliant with EN 50121-3-2, EN 50121-4, and a portion of the EN 50155 specifications. In addition, these modules all support a wide operating temperature range of -40 to 75°C for reliable operation even in harsh environments.

Specification

Voltage 24 VDC
Connector Spring-type Euroblock terminal
Counter Frequency 5 kHz
Dry Contact On: short to GND
Off: open
I/O Mode DI, event counter, or frequency
Points per COM 8 channels
Sensor Type Dry contact
Wet Contact (NPN or PNP)
Wet Contact (DI to GND) On: 10 to 30 VDC
Off: 0 to 3 VDC

Voltage 24 VDC
Connector Spring-type Euroblock terminal
Current Rating 200 mA per channel
I/O Type Sink
I/O Mode DO or PWM
Over-Current Protection 0.65 A per channel @ 25°C
Over-Temperature Shutdown 175°C (typical), 150°C (min.)
Over-Voltage Protection 85M-2600-T: 45 VDC (typical)
45 VDC (typical)
Pulse Output Frequency 5 kHz

Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Built-in Resistor for Current Input 85M-3800-T/3801-T: 125 ohms
Connector Spring-type Euroblock terminal
Historical Data Buffering 85M-3801-T/3811-T: 60 KB per channel, 6-second data buffer at 5 kHz
I/O Type Differential
Input Impedance 85M-3800-T/3801-T: 125 ohms (min.)
85M-3810-T: 200 kilo-ohms (min.)
85M-3811-T: 20 mega-ohms (min.)
Input Range 85M-3800-T/3801-T: 4 to 20 mA (with burn-out detection)
85M-3810-T/3811-T: 0 to 10 VDC
Resolution 16 bits
Sampling Rate 85M-3800-T/3810-T:
All channels: 100 samples/sec
Per channel: 12.5 samples/sec
85M-3801-T/3811-T: All channels: 40k samples/sec
Per channel: 5k samples/sec

Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Connector Spring-type Euroblock terminal
Input Connection 2- or 3-wire
Input Impedance 625 kilo-ohms (min.)
Sensor Type JPT100, JPT200, JPT500 (-200 to 640°C)
JPT1000 (-200 to 350°C)
NI100, NI50, NI500 (-60 to 250°C)
NI1000 (-60 to 150°C)
NI120 (-80 to 260°C)
PT1000 (-200 to 350°C)
PT50, PT100, PT200, PT500 (-200 to 850°C)
Resistance of 310, 620, 1250, and 2200 ohms
Resolution 0.1°C or 0.1 ohms
Sampling Rate All channels: 12 samples/sec
Per channel: 2 samples/sec

Millivolt Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
Connector Spring-type Euroblock terminal
Input Impedance 1 mega-ohms (min.)
Millivolt Type ±19.532 mV
±39.062 mV
±78.126 mV
Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on)
Resolution 16 bits
Sampling Rate All channels: 12 samples/sec
Per channel: 1.5 samples/sec
Sensor Type J, K, T, E, R, S, B, N

Baudrate 300 bps to 921.6 kbps
Parity None, Even, Odd
Serial Standards RS-232/422/485
Data Bits 7, 8
Stop Bits 1, 2

RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND

Power Consumption 85M-1602-T: 50.0 mA @ 24 VDC
85M-2600-T: 35.4 mA @ 24 VDC
85M-3800-T: 43.8 mA @ 24 VDC
85M-3801-T: 43.8 mA @ 24 VDC
85M-3810-T: 43.3 mA @ 24 VDC
85M-3811-T: 521 mA @ 24 VDC
85M-5401-T: 51.7 mA @ 24 VDC
85M-6600-T: 27.7 mA @ 24 VDC
85M-6810-T: 24.1 mA @ 24 VDC

Dimensions 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
Weight Under 80 g
Wiring I/O cable, 14 to 28 AWG

Operating Temperature -40 to 75°C (-40 to 167°F)
Storage Temperature (package included) -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.

Safety UL 508
EMC EN 55032/24
EN 61000-6-2/-6-4
EMI CISPR 32, FCC Part 15B Class A
EMS IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
Railway EN 50121-4
EN 50155 (complies with a portion of EN 50155 specifications)

Time 85M-1602-T: 1,132,561 hrs
85M-2600-T: 792,571 hrs
85M-3800-T: 1,512,906 hrs
85M-3801-T: 1,426,112 hrs
85M-3810-T: 1,530,690 hrs
85M-3811-T: 1,426,112 hrs
85M-5401-T: 596,611 hrs
85M-6600-T: 571,446 hrs
85M-6810-T: 2,324,891 hrs
Standards Telcordia SR332

Warranty Period 5 years
Details See www.moxa.com/warranty

Models